GOTH-1420 GOTH-1100 GOTHO-1420 GOTHO-1420Pt100 GOTHO-1420Pt1000 GOTHO-1420N3K戶外用溫濕度變送器OUTSIDE TEMP./HUMI. TRANSMITTER OUTSIDE TEMP./HUMI. TRANSMITTER(GOTH-1420) | | | "GOTH" Outside Temperature Humidity Transmitter is intended for ventilation and air-handling units to detect outside temperature and relative humidity. Especially, This unit is very suitable for using in pulp/textile/food warehouse, greenhouse, computer room, R&D room, indoor swimming pool, hospital, etc. | | This unit can be used with all system equipments that can receive output signals 4-20mA DC of the detector. | | Relative Humidity 1) This Transmitter senses relative humidity by chargeable humidity sensing element which varies electrical capacity depending on circumstantial relative humidity. 2) Electronic sensing circuit varies signal into 4 ~ 20mADC ( within 0 ~ 99% relative humidity ) Temperature This Transmitter senses temperature by sensing element of PT1000Ω which varies electrical resistance depending on sensing temperature | | SUPPLY VOLTAGE | : 24V AC/DC ±20%
| | FREQUENCY | : 50 or 60㎐ | SENSING ELEMENT | : Integrated Circuity | | POWER CONSUMPTION | : below 1VA | | SENSING RANGE | : -35~+80℃ / 0 ~ 99%RH | | ACCURACY | : 20°C at 20~90%Rh with in ±3%Rh
| | OUTPUT SIGNAL | : Pt1000Ω (Pt100Ω) / 4 ~ 20mA DC | | SENSING TIME | : Apprx. 20 sec | | | AMBIENT TEMPERATURE | : 1) On Operation : -30 ~ +80℃ 2) On Transportation & Storage : -25 ~ +65°C
| | AMBIENT HUMIDITY | : On Operation : below 95%Rh | | WIRING | : 2and 3wires, 1.0㎡ | | WEIGHT | : 0.06Kg
| | HOUSING | : plastic case
| PROTECTION CLASS | : IP 30 | | | Select a location approx 1.5 meter above the floor. The sensor location should also be reasonably clean and free damp and condensation. The element must not to be touched and should be protected from dust, water, spray and condensation. The sensor element must not to be exposed to organic solvents, sylphid bearing materials. Do not use DC test meter as this will damage the sensor element. Fix with the bolts provided in pull box (50x100) To avoid the conductive current the wires should be separated from power lines. Use the shield line when wiring. | | OUTSIDE TEMP./HUMI. TRANSMITTER(GOTH-1100) | | | "GOTH" Outside Temperature Humidity Transmitter is intended for ventilation and air-handling units to detect outside temperature and relative humidity. Especially, This unit is very suitable for using in pulp/textile/food warehouse, greenhouse, computer room, R&D room, indoor swimming pool, hospital, etc. | | This unit can be used with all system equipments that can receive output signals 0-10VDC of the detector. | | Relative Humidity 1) This Transmitter senses relative humidity by chargeable humidity sensing element which varies electrical capacity depending on circumstantial relative humidity. 2) Electronic sensing circuit varies signal into 0-10VDC ( within 0 ~ 99% relative humidity ) Temperature This Transmitter senses temperature by sensing element of PT1000Ω which varies electrical resistance depending on sensing temperature | | SUPPLY VOLTAGE | : 24V AC/DC ±20%
| | FREQUENCY | : 50 or 60㎐ | SENSING ELEMENT | : Integrated Circuity | | POWER CONSUMPTION | : below 1VA | | SENSING RANGE | : -35~+80℃ / 0 ~ 99%RH | | ACCURACY | : 20°C at 20~90%Rh with in ±3%Rh
| | OUTPUT SIGNAL | : Pt1000Ω (Pt100Ω) / 4 ~ 20mA DC | | SENSING TIME | : Apprx. 20 sec | | | AMBIENT TEMPERATURE | : 1) On Operation : -10 ~ +70℃ 2) On Transportation & Storage : -25 ~ +65°C
| | AMBIENT HUMIDITY | : On Operation : below 95%Rh | | WIRING | : 2and 3wires, 1.0㎡ | | WEIGHT | : 0.06Kg
| | HOUSING | : plastic case
| PROTECTION CLASS | : IIP 30 | | | Select a location approx 1.5 meter above the floor. The sensor location should also be reasonably clean and free damp and condensation. The element must not to be touched and should be protected from dust, water, spray and condensation. The sensor element must not to be exposed to organic solvents, sylphid bearing materials. Do not use DC test meter as this will damage the sensor element. Fix with the bolts provided in pull box (50x100) To avoid the conductive current the wires should be separated from power lines. Use the shield line when wiring | OUTSIDE TEMP./HUMI. TRANSMITTER(GOTHO-1420) | | | “ GOTHO “ Outside Air temperature & Humidity Transmitter is intended for controlling Sensor by detecting relative humidity and temperature of outside air for ventilation and air-handling units. This unit can also be used as Interface detector used with display of sensing value or Auto control system of building | | Pulp/Textile warehouse, Greenhouse, Computer room, R&D room, Hospital, etc. Use measuring detector : In case of Optimistic function system | | SUPPLY VOLTAGE : DC 15~30V OUTPUT SIGNAL : Current / 4 ~ 20mA SENSING RANGE : Temperature /-20 ~ +50°C , Humidity / 0 ~ 99%RH SENSING ELEMENT : Pt1000Ω / Integrated Circuity SELF-GENERATING CURRENT : below 2mA ( 0.02 OHM / 0.05 Deg.) ACCURACY : at 20°C within ±0.3°C, at 10 ~ 90%RH, ±3%RH WIRING : 4 Wire SENSING TIME : 1 minute apprx AMBIENT TEMPERATURE 1) On Operation : -30 ~ +70°C 2) On Transportation & Storage : -20 ~ +50°C AMBIENT HUMIDITY 1) On Operation : below 99%Rh 2) On Transportation & Storage : below 95%Rh PROTECTION CLASS ENCLOSURE : IP30 (EN60529) WEIGHT : 0.10 Kg | | Engineering 1) In case of control : Preferably install on the wall of building or house and keep away from direct light, | | 1) Installation height ; Preferably install in the middle of house, building or heating area, and to be installed at least 1.5 meter above from the floor. 2) Prohibited Location ; Window, door, Ventilating hole, upper place of heat source, and Veranda or beneath the eaves of roof. 3) To prevent any detecting errors from convection of warm air, cable wire tube of transmitter should be shielded and must not be painted | | OUTSIDE TEMP./HUMI. TRANSMITTER(GOTHO-1420Pt100) | | | “ GOTHO “ Outside Air temperature & Humidity Transmitter is intended for controlling Sensor by detecting relative humidity and temperature of outside air for ventilation and air-handling units. This unit can also be used as Interface detector used with display of sensing value or Auto control system of building | | Pulp/Textile warehouse, Greenhouse, Computer room, R&D room, Hospital, etc. Use measuring detector : In case of Optimistic function system | | SUPPLY VOLTAGE | : 15 ~ 30V DC | | OUTPUT SIGNAL | : Temperature / Pt100Ω, Humidity / 4 ~ 20mA
| | | SENSING RANGE | : Temperature / -35 ~ + 80°C, Humidity / 0 ~ 99%RH
| SENSING ELEMENT | : Pt 100Ω / Integrated Circuity | | TEMPERATURE CO-EFFICIENT | : 0.00385 OHMS | SELF-GENERATING CURRENT | : below 2mA
| | | ACCURACY | : at 25°C within ±0.3°C, at 10 ~ 90%RH, within ±3%RH
| | | WIRING | : 4 Wire | | SENSING TIME | : 1 minute apprx. | | | AMBIENT TEMPERATURE | : 1) On Operation : -30 ~ +70°C 2) On Transportation & Storage : -20 ~ +50°C
| | PAMBIENT HUMIDITY | : 1) On Operation : below 99%Rh 2) On Transportation & Storage :below 95%Rh | PROTECTION CLASS | : IP30 (EN60529)
| WEIGHT | : 0.10 Kg | | | | Engineering 1) In case of control : Preferably install on the wall of building or house and keep away from direct light. | 1) Installation height ; Preferably install in the middle of house, building or heating area, and to be installed at least 1.5 meter above from the floor. 2) Prohibited Location ; Window, door, Ventilating hole, upper place of heat source, and Veranda or beneath the eaves of roof. 3) To prevent any detecting errors from convection of warm air, cable wire tube of transmitter should be shielded and must not be painted | | | OUTSIDE TEMP./HUMI. TRANSMITTER(GOTHO-1420Pt1000) | | | “ GOTHO “ Outside Air temperature & Humidity Transmitter is intended for controlling Sensor by detecting relative humidity and temperature of outside air for ventilation and air-handling units. This unit can also be used as Interface detector used with display of sensing value or Auto control system of building | | Pulp/Textile warehouse, Greenhouse, Computer room, R&D room, Hospital, etc. Use measuring detector : In case of Optimistic function system | | SUPPLY VOLTAGE | : 15 ~ 30V DC | | OUTPUT SIGNAL | : Temperature / Pt1000Ω, Humidity / 4 ~ 20mA
| | | SENSING RANGE | : Temperature / -35 ~ + 80°C, Humidity / 0 ~ 99%RH
| SENSING ELEMENT | : Pt 1000Ω / Integrated Circuity | | TEMPERATURE CO-EFFICIENT | : 0.00385 OHMS | SELF-GENERATING CURRENT | : below 2mA
| | | ACCURACY | : at 25°C within ±0.3°C, at 10 ~ 90%RH, within ±3%RH
| | | WIRING | : 4 Wire | | SENSING TIME | : 1 minute apprx. | | | AMBIENT TEMPERATURE | : 1) On Operation : -30 ~ +70°C 2) On Transportation & Storage : -20 ~ +50°C
| | PAMBIENT HUMIDITY | : 1) On Operation : below 99%Rh 2) On Transportation & Storage :below 95%Rh | PROTECTION CLASS | : IP30 (EN60529)
| WEIGHT | : 0.10 Kg | | | | Engineering 1) In case of control : Preferably install on the wall of building or house and keep away from direct light. | | | OUTSIDE TEMP./HUMI. TRANSMITTER(GOTHO-1420N3K) | | | “ GOTHO “ Outside Air temperature & Humidity Transmitter is intended for controlling Sensor by detecting relative humidity and temperature of outside air for ventilation and air-handling units. This unit can also be used as Interface detector used with display of sensing value or Auto control system of building | | Pulp/Textile warehouse, Greenhouse, Computer room, R&D room, Hospital, etc. Use measuring detector : In case of Optimistic function system | | SUPPLY VOLTAGE | : 15 ~ 30V DC | | OUTPUT SIGNAL | : Temperature / NTC 3KΩ, Humidity / 4 ~ 20mA
| | | SENSING RANGE | : Temperature / -25 ~ + 80°C, Humidity / 0 ~ 99%RH
| SENSING ELEMENT | : NTC 3KΩ / Integrated Circuity | | TEMPERATURE CO-EFFICIENT | : 0.00385 OHMS | SELF-GENERATING CURRENT | : below 2mA(0.02 OHM / 0.05Deg.)
| | | ACCURACY | : at 25°C within ±0.3°C, at 10 ~ 90%RH, within ±3%RH
| | | WIRING | : 4 Wire | | SENSING TIME | : 1 minute apprx. | | | AMBIENT TEMPERATURE | : 1) On Operation : -25 ~ +70°C 2) On Transportation & Storage : -15 ~ +60°C
| | PAMBIENT HUMIDITY | : 1) On Operation : below 99%Rh 2) On Transportation & Storage :below 95%Rh | PROTECTION CLASS | : IP30 (EN60529)
| WEIGHT | : 0.10 Kg | | | | Engineering 1) In case of control : Preferably install on the wall of building or house and keep away from direct light. | | |