CDI-RTD隔離電阻溫度變換器Isolation RTD temperature converter
CDI-RTD Accepts RTD temperature sensor signalCDI-signal, and provides isolated DC outputs. MODEL: CDI-RTD MODEL TYPE INPUT OUTPUT 1 POWER 1 : 1 Output 2 : 2 Output A : 1 Output with display B : 2 Output with display X : AC 110V or 220V for 50/60Hz Y : DC 24V Z : Other special power - Construction : Plug -in - Wring : M3.5 Screw Terminal - Isolation : Power to Input to Output1 to Output2 - Adjustment : Zero & Span± 20% of full scale - Operating temperature : -5℃ ~ 55℃ - Operating humidity : 90%RH Max (none condensing) - Power supply AC : 110V or 220V/60Hz ±10%,approx 3VA DC : 18V ~ 30V ±10%,approx 3VA - Power selection : AC 110V/220V Swich in the back plane - Mounting : Wall or DIN rail - Accuracy : ± 0.1% - Temp'coefficient : ±0.015/℃ - Response time : 0.5 Sec or less(0~90%) - Insulation resistance : 100MΩor more with 500VDC(Input/Output/Power) - Dielectric strength : 1500VAC at 1minute (Input to Output to Power) 1 : Jpt 100Ω(JIS'89) 2 : Pt 100Ω 3 : Pt 1000Ω 4 : Other special spec CDI TECH CO.,LTD. MODEL CDI - RTD RTD TEMPERATURE CONVERTER GENERAL SPECIFICATION INPUT - 2 Wire or 3Wire type - Range : -200 ~ 600℃ - Sensor type : Pt 100Ω or Pt 1000Ω (JIS or DIN) - Sensing current : 1.5mA - DC VOLTAGE : ±12V Max - Load Resistance Output Resistance 0 ~ 10mV 1KΩor more 0 ~ 100mV 1KΩ or more 0 ~ 1V 1KΩ or more 0 ~ 5V 2KΩ or more 0 ~ 10V 4KΩ or more -10V ~ 10V 4KΩ or more - DC CURRENT : 0 ~ 20mA - Load Resistance Output Resistance 0 ~ 1mA 15KΩor less 0 ~ 10mA 1.5KΩ or less 0 ~ 20mA 750Ω or less 1 ~ 5mA 3KΩ or less 4 ~ 20mA 750Ω or less OUTPUT INSTALLATION PERFORMANCE ORDERING CODE SELECTION