GDH-420 GDH-110 GDHO-420膽管濕度變送器

返回列表頁
參  考  價面議
具體成交價以合同協議為準

產品型號

品       牌

廠商性質經銷商

所  在  地中山市

聯系方式:黃玲查看聯系方式

更新時間:2024-10-29 10:03:54瀏覽次數:79次

聯系我時,請告知來自 智能制造網


    暫無信息

經營模式:經銷商

商鋪產品:2203條

所在地區:廣東

聯系人:黃玲 (業務)

產品簡介

GDH-420 GDH-110 GDHO-420膽管濕度變送器

詳細介紹

 

DUCT HUMIDITY TRANSMITTER(GDH-420)
"GDH" Duct Humidity Transmitter is intended for an electronic Humidity transmitter to measures the Duct Relative Humidity (RH) and converts the measurement into and electric signal.
This unit can be used with all system equipments that can receive output signals 4 ~ 20mA DC of the detector.
This Transmitter senses relative humidity by chargeable humidity sensing element which varies electrical capacity depending on circumstantial relative humidity.
Electronic sensing circuit varies signal into 4 ~ 20mA DC ( within 0 ~ 99% relative humidity ).
Sensing Accuracy is ±3% within usable range of 20 ~ 90% RH.

SUPPLY VOLTAGE

: 24V AC/DC ±20%

FREQUENCY

: 50 or 60㎐

POWER CONSUMPTION

: below 0.5VA

SENSING RANGE

: 0 ~  99% Rh

SENSING ELEMENT

: Integrated Circuity

ACCURACY

: 20°C at 20~90%Rh with in ±3%Rh

OUTPUT SIGNAL

: 4 ~ 20mA DC

SENSING TIME

: Apprx. 20 sec. (velocity 20m/s)

AMBIENT TEMPERATURE

: 1) On Operation : -5 ~ +50℃
  2) On Transportation & Storage : -25  ~ +70°C

AMBIENT HUMIDITY

: 1) On Operation : 5 ~ 99%Rh
  2) On Transportation  : below 95% Rh

WEIGHT

: 0.17Kg (W/BRACKET)

CABLE FITTING

: PF 1/2"

PROTECTION CLASS

: IP 54

Installation Location; When the detector has to be mounted on supply duct, the detector must be kept
between 3 to 8 meters from the humidifier unit
For accurate measurement of the relative humidity, Follow recommendation as ;
-Steam humidifier; between 5 to 8 meters
-Spray water fogger; between 3 to 10 meters
DUCT HUMIDITY TRANSMITTER(GDH-110)
"GDH" Duct Humidity Transmitter is intended for an electronic Humidity transmitter to measures the Duct Relative Humidity (RH) and converts the measurement into and electric signal.
This unit can be used with all system equipments that can receive output signals 0 ~ 10VDC of the detector.

This Transmitter senses relative humidity by chargeable humidity sensing element which varies electrical capacity depending on circumstantial relative humidity.
Electronic sensing circuit varies signal into 0 ~ 10VDC ( within 0 ~ 99% relative humidity ).
Sensing Accuracy is ±3% within usable range of 20 ~ 90% RH.

SUPPLY VOLTAGE

: 24V AC/DC ±20%

FREQUENCY

: 50 or 60㎐

POWER CONSUMPTION

: below 0.5VA

SENSING RANGE

: 0 ~ 99% Rh

SENSING ELEMENT

: Integrated Circuity

ACCURACY

: 20°C at 20~90%Rh with in ±3%Rh

OUTPUT SIGNAL

: 0 ~ 10V DC (0 ~ 1V DC)

SENSING TIME

: Apprx. 20 sec(velocity 20m/s)

AMBIENT TEMPERATURE

: 1) On Operation : -5 ~ +50℃
2) On Transportation & Storage : -25 ~ +70°C

AMBIENT HUMIDITY

: 1) On Operation : 5 ~ 99%Rh
2) On Transportation : below 95% Rh

WEIGHT

: 0.17Kg (W/BRACKET)

CABLE FITTING

: PF 1/2"

PROTECTION CLASS

: IP 54

DUCT HUMIDITY TRANSMITTER(GDHO-420)

"GDHO “ Duct Humidity Transmitter is intended for Ventilation and Air-handling units to the following usages ;
Sensing supplying or ventilating Air humidity
Shift Sensor ( in case of revising room humidity depend on outside air humidity )
Measuring Sensor ( display sensing value or in case of using DDC auto control system )

SUPPLY VOLTAGE

: 15 ~ 30 V DC

OUTPUT SIGNAL

: 4 ~ 20 mA

SENSING RANGE

: 0 ~ 99%RH

SENSING ELEMENT

: Integrated Circuity

ACCURACY

: 20°C at 20~90%Rh within ± 3%Rh

WIRING

: 2 Wire

SENSING TIME

: Apprx.1 min. at 2m/s velocity

AMBIENT TEMPERATURE

: -5 ~ +70°C

AMBIENT HUMIDITY

: 1) On Operation : below 5 ~ 99%RH
  2) On Transportation : below 95%RH

CABLE FITTING

: PF1/2"

PROTECTION CLASS

: IIP54 (EN60529)

WEIGHT

: 0.25Kg ( including bracket )

In case of controlling supplying air humidity
- In case of installing Fan at the last air control unit, install behind of Fan
- For the other cases, install at least 1.5M away from the last air control unit
In case of controlling ventilating air humidity
- Install always at behind of Fan


感興趣的產品PRODUCTS YOU ARE INTERESTED IN

智能制造網 設計制作,未經允許翻錄必究 .? ? ? Copyright(C)?2021 http://www.xashilian.com,All rights reserved.

以上信息由企業自行提供,信息內容的真實性、準確性和合法性由相關企業負責,智能制造網對此不承擔任何保證責任。 溫馨提示:為規避購買風險,建議您在購買產品前務必確認供應商資質及產品質量。

會員登錄

×

請輸入賬號

請輸入密碼

=

請輸驗證碼

收藏該商鋪

登錄 后再收藏

提示

您的留言已提交成功!我們將在第一時間回復您~
主站蜘蛛池模板: 嫩江县| 塔河县| 定兴县| 永靖县| 胶州市| 乐清市| 洮南市| 无棣县| 会泽县| 油尖旺区| 长宁区| 福泉市| 商河县| 遵义县| 吉隆县| 延川县| 桃园市| 长宁县| 武宣县| 绍兴市| 长汀县| 天等县| 庆安县| 西安市| 左贡县| 巴塘县| 乐业县| 鹤峰县| 沂南县| 桦川县| 昌黎县| 浪卡子县| 礼泉县| 靖宇县| 崇文区| 水富县| 葵青区| 施秉县| 博客| 都匀市| 东丽区|