Rating |
DOG-M51 (Non Draw out) DOG-M51 (Draw out) |
Rating |
Rated current Frequency Auxiliary Voltage Ambient temperature | 1AC 5A 150/60Hz ±5% 1AC/DC 110V (80) 1-10℃ to +60℃ |
Current Setting |
-OC- Overcurrent range Instantaneous -EF- Overcurrent range Instantaneous | 12~10A/steps of 0.5A 120~80A/steps of 5A
10.2~2A/steps of 0.05A 11~40A /steps of 0.5A |
Time Setting & Curve |
-OC- Overcurrent time Lever Instantaneous *Normal inverse time
*Very inverse time
*Extremely inverse time
*Definite time Resetting Value Reset time | 10.25~40 Lever (steps of 0.25 lever) 1Less than 40 | ※ I : Fault current(%) ※ tp : time lever | 1> 95% 1< 100ms |
Burden |
Overcurrent Earth Fault Aux. Voltage | 0.5VA 0.5VA 12VA(AC), 6W(DC) |
Contacts |
Output Relay Trip & Alarm contact capacity 111111111111111111111111111111111 Make 111111111111111111111111111111111Break | OC : Trip 1c, Alarm 1a AC 240V 10A (L/R=0ms) DC 1000W 0.5sec (L/R=0ms) AC 240V 3A (L/R=0ms) DC 30W 0.5sec (L/R=0ms) |
Indicator |
Operating start CPU RUN Operating | LED(Red) LED(Green) LED(Red)Manual Reset |
Operating time |
Over Current Normal inverse time Very inverse time Extremely inverse time | Earth Fault Normal inverse time Very inverse time Extremely inverse time Instantaneous time | | Lever #10 300% 6.3sec 700% 3.5sec 300% 6.75sec 700% 2.25sec 300% 10sec 700% 1.67sec | Lever #5 300% 3.15sec 700% 1.76sec 300% 3.37sec 700% 1.12sec 300% 5.0sec 700% 0.83sec Lessthan 0.01sec | |
1Degree Protection | 1IP52 |
1Thermal Withstand Capability | 1For 1s 80×In Continuously 3×In |
1Malfunction | 110Hz 5mm double amplitude 30s each in X and Y directions 116Hz 2.5mm double amplitude 600s each in X, Y and Z 1directions |
1Destruction | 1300㎨(approx. 30G) 3times each in 3 directions |
1Dielectric Withstand 1Insulation resistance at 500V 1Impulse Voltage Withstand 1Surge transient simulator 1Weight | 12kV for 1minute between all terminals and case earthed. 1 >100㏁ 15kV-1.2/50㎲ 12.5kV 1㎒/200Ω 12.2㎏ |